CanServo/Manual/Summary/en
Under Construction
Overview of this page
CAN servo is a servo controlled through CAN communication. It supports CAN 2.0A, 2.0B and supports DroneCAN protocol.
This document summarizes the contents of the CAN Servo Manual and rearranges them from a functional point of view. For details, refer to the CAN servo manual.
F/W Types
It is divided according to the type of protocol supported.
- C Type = support CAN 2.0A, 2.0B
- U Type = support DroneCAN
- A Type = support CAN 2.0A, 2.0B, DroneCAN
Simple Test
C Type or A Type: The factory default setting of CAN servo is CAN 2.0A, 1000kbps, Servo Mode. For testing purposes, we send the following packets:
- CAN 2.0A packet, CAN ID = 0, DATA = 'w', 0, 0x1E, 0xAA, 0x2A, DLC = 5 ---> Move to +60 degree position
- CAN 2.0A packet, CAN ID = 0, DATA = 'w', 0, 0x1E, 0x00, 0x20, DLC = 5 ---> Move to 0 degree position
Communication settings
- Communication settings are applied at the time of Servo Reset.
- If you are using CAN communication for the first time, please refer to CAN/Overview.
CAN baudrate
Select the communication speed to use. The unit is kbps.
- Register Address: 0x38
- 0 - 1000
- 1 - 800
- 2 - 750
- 3 - 500
- 4 - 400
- 5 - 250
- 6 - 200
- 7 - 150
- 8 - 125
Select Protocol
Select the protocol type to be used for communication through CanServo/MODE/CAN/en.
Select from CAN 2.0A, 2.0B, or DroneCAN. Depending on the protocol, it may be necessary to change the FW Type.
The reason CAN 2.0A and B are divided is because the CAN ID value must also match, but the Type is also checked. That is, CAN ID = 100 with CAN 2.0A and CAN ID = 100 with CAN 2.0B are recognized differently.
- For details, refer to CanServo/Packet Accept Rule/en.
According to the status of CanServo/MODE/CAN/en, the following protocol is followed.
- CAN 2.0A, 2.0B: CanServo/Protocol/Control/en
- DroneCAN: CanServo/Protocol/UAVCAN/en
Servo ID designation
To control servos, you need to distinguish between servos. Servos are distinguished by two types of IDs.
- When using CAN 2.0A, 2.0B protocol, it is divided into CAN ID and Servo ID.
- When using DroneCAN, it is divided into Node ID and Actuator ID.
Set each ID:
- CAN ID and Node ID are set through Register CanServo/ID2/en.
- Servo ID and Actuator ID are set through Register CanServo/ID1/en.
Operation Mode
- CAN servo supports Servo Mode that operates within one rotation and Turn Mode that allows +/-32760 x 360 deg operation.
- Note: When Turn Mode is selected, the position at the time of servo reset becomes 0 deg, 0 Turn position.
- Choose from 2 options.
- Operation mode is applied at the time of servo reset.
- Please refer to Register CanServo/MODE/RUN/en.
Servo control method
- CAN servo has 128 registers of 2 byte size.
- It operates according to these values.
- For example
- In Servo Mode, if you set a value of 8192 in Register POSITION_NEW, it moves to the center position.
- If you read the Register CanServo/POSITION/en value, you can know the current position of the servo.
- CanServo/Protocol/Control/en
- CanServo/Register/en
- CanServo/Register/Write/en
- CanServo/Register/Read/en
Applied time when setting value is changed
- Most user-use settings take effect immediately after change.
- But, the following items, as an exception, are applied at the time of Servo Reset, so SAVE and RESET procedures must be performed.
- Communication settings: communication speed, communication protocol, ID2, ID1
- Operation mode ( CanServo/MODE/RUN/en )
- Stream CAN ID set value ( CanServo/Stream/CAN ID/en )
Storage of setting value
- Most of the registers are saved at the time of SAVE command and are maintained even after Servo Reset.
- Exceptions are:
- Control values (POSITION_NEW, TURN_NEW, etc.)
- Various status values (ex: POSITION)
- Other exceptions
- Exceptions are:
- !!! caution !!!
- It is recommended to do SAVE with the motor stopped.
- You should not SAVE too often.
- In particular, this should not be done periodically.
- After changing as many values as possible, it is recommended to SAVE and Servo Reset.
- However, it is recommended to change or reset the communication setting value, ID, RUN_MODE, etc., not together with other values.
Location coordinate system
- CanServo/POSITION, POSITION_NEW: Resolution: 16384 = 360 deg
Servo Mode
- This mode operates within 1 rotation.
- Set the desired position in Register POSITION_NEW.
- Range: 0 ~ 16383
- Center: 8192
- You can limit the range of motion with POSITION_MIN, POSITION_MAX.
Turn Mode
- Multi-rotation position control mode.
- It works if you set the number of rotations in CanServo/TURN_NEW/en and set the angle within 360 degrees in CanServo/POSITION_NEW/en.
- Both values follow the int16_t ( 16 bits signed integer ) method, so negative numbers can be specified.
- !!! caution !!!
- When the servo is reset, the position value is initialized to 0.
- Immediately after Servo Reset, if TURN_NEW = 0, POSITION_NEW = 0 is transmitted, it remains motionless.
- It is recommended to use the 'W' Write message that can transmit two registers at the same time.
- When transmitting separately, an error occurs in either of the two transmissions, resulting in undesirable behavior.
DroneCAN UNITLESS Coordinate System
- If you use UNITLESS mode when designating the target position in DroneCAN Actuator.ArrayCommand message, you can specify from -1.0000 to +1.0000 in normalized form.
- The position values specified in this way are converted to actual position values from -1 to 0 to +1 ---> POSITION_MIN, POSITION_MID, and POSITION_MAX.
- For example, -0.5000 becomes (POSITION_MIN+POSITION_MID)/2 .
Communication example
For example, if you have 4 servos as
- S1: PROTOCOL=2.0A, ID2 = 10, ID1 = 101
- S2: PROTOCOL=2.0A, ID2 = 20, ID1 = 102
- S3: PROTOCOL=2.0B, ID2 = 10, ID1 = 103
- S4: PROTOCOL=2.0B, ID2 = 20, ID1 = 104
Assuming that the value 0x11 is written to register 0x30 of S2 servo
- CAN ID = 0, TYPE=2.0A, DATA = 'w', 102, 0x30, 0x11, 0x00 -> Received and processed by S2
- CAN ID = 0, TYPE=2.0B, DATA = 'w', 102, 0x30, 0x11, 0x00 -> S2 ignored, TYPE incorrect
To explain the DATA part,
- The first byte 'w' means the command to write 1 Register.
- Refer to CanServo/Protocol/Control/en for details.
- The second byte 102 means Target Servo ID, and since it is 102, it points to S2.
Basic usage
Change target position
You can specify the target position through *Register POSITION_NEW.
- In Turn Mode, Register TURN_NEW is used together.
- Register TURN_NEW is ignored in Servo Mode.
- POSITION_NEW and TURN_NEW are not saved.
- In Turn Mode, there are two ways to specify the target position, depending on whether POSITION_NEW is used as a negative number.
- Let's take the following three examples.
- -370 deg = -370 x 16384 / 360 = -16839.111 = -16839
- -10 deg = -10 x 16384 / 360 = -455.111 = -455
- 10 deg = 10 x 16384 / 360 = 455.111 = 455
- -370 deg
- TURN_NEW = -1, POSITION_NEW = -455 -> when using negative numbers
- TURN_NEW = -2, POSITION_NEW = 15929 -> When not to use negative numbers
- -10 deg
- TURN_NEW = 0, POSITION_NEW = -455 -> when using negative numbers
- TURN_NEW = -1, POSITION_NEW = 15929 -> When not to use negative numbers
- 10 deg
- TURN_NEW = 0, POSITION_NEW = 455
- Let's take the following three examples.
- Calculating TURN_NEW, POSITION_NEW in Turn Mode
- Change the target angle (deg) in POSITION units.
- pos = (integer conversion) ( deg x 16384 / 360 )
- turn and the remainder.
- TURN_NEW = (convert to round off) (pos / 16384)
- POSITION_NEW = pos % 16384 ( C style )
- Transmit two values (Type 1)
- POSITION_NEW can be less than 0 here.
- If you change POSITION_NEW to a positive number, set CanServo/TURN to -1. (Type 2)
- Change the target angle (deg) in POSITION units.
int32_t pos = (int32_t)(deg * 16384 / 360); int32_t turn = pos / 16384; int32_t posi = pos % 16834; // TYPE 1: send 'W' command: turn -> TURN_NEW, posi -> POSITION_NEW while( posi < 0 ) { posi += 16384; turn -= 1; } // TYPE 2: send 'W' command: turn -> TURN_NEW, posi -> POSITION_NEW
Limiting the target position
- In Servo Mode, you can specify the operating range in Register POSITION_MIN and POSITION_MAX.
- Resolution is 16384 = 360 deg.
- Recommended maximum range of motion: Center (8192) +/- 150 degrees
- For example, if you specify +/- 60 degrees
- 60 deg = 60 x 16384 / 360 = 2730
- POSITION_MIN = -60 deg = 8192 - 2730 = 5462
- POSITION_MAX = +60 deg = 8192 + 2730 = 10922
Read current location
The servo's current position value is provided in various formats.
Register
- CanServo/POSITION/en - Position value within 1 rotation
- CanServo/TURN/en - rotation status
- CanServo/POSITION-32/en - 32-bit position value with rotation state combined
- CanServo/POSITION-32/LOW/en - When reading only Low Word from 32-bit position value
Read value:
- In Servo Mode, read Register POSITION or POSITION-32-LOW.
- In Turn Mode, read Register POSITION, TURN. Or read POSITION-32.
The difference between POSITION and POSITION-32-LOW
- POSITION is stored only from 0 to 16383, and the change in TURN is known only by reading TURN.
- POSITION-32-LOW has 2 additional bits, so you can know the status up to 4 turns back and forth.
속도 바꾸기
- 동작 최대 속도를 지정할수 있습니다.
- 0 으로 변경하면 목표 위치를 바꾸더라도 움직이지 않습니다.
CAN 서보에서 속도의 단위는 pos/100msec 입니다.
pos 의 단위는 16384 = 360 deg 입니다.
Vt (sec/60deg) 와 Vp (pos/100msec) 의 변환식은 다음과 같습니다. 단, PT = Reg PID TIME, PX = PT / 10
- Vp = 60 x 16384 / 360 / Vt / 10 x PX
- Vt = 60 x 16384 / 360 / Vp / 10 x PX
ex) 1920 pos/100msec = 0.142 sec/60deg, PX=1
ex) 1920 pos/100msec = 0.284 sec/60deg, PX=2
토크 바꾸기
- 최대 출력을 조절합니다.
- 최대 속도도 비례적으로 조정됩니다.
- 0 으로 변경하면 힘이 완전히 풀리면서 외력에 의해 움직일수 있습니다.
OLP
- Over Load Protection 기능입니다.
- 지정한 시간 이상 내부 제어기 출력이 Full 이 되면, 발동합니다.
- OLP 가 발동하면, OLP Ratio 로 지정된 값으로 출력이 조정됩니다.
- 90 이면 출력이 90% 가 됩니다.
- OLP 발동 시간은 PX = PT / 10, PT = PID TIME 에 의해 달라집니다.
- OLP 발동시간 = OLP Time x PX 입니다.
- PX = 2 이고 OLP Time = 3 이면, OLP 발동 시간은 6초가 됩니다.
비상 정지
- 일시적으로 서보 이동을 멈춥니다.
- 이 상태는 저장되지 않으며, 서보 Reset 후에는 풀립니다.
- 비상 정지 상태에 따라 정지까지의 과정과 상태 유지 방식이 다릅니다.
- 0 = 비상 정지 해제
- 1 = 즉시 모터 출력을 끕니다. 외력에 의해 움직일수 있습니다.
- 2 = Time Speed ES 값에 맞추어 감속하고, 정지 위치를 고수합니다.
- 3 = 즉시 멈추고, 정지 위치를 고수합니다.
전압, MCU 온도에 따른 비상 정지
- MCU 온도와 전압의 상태가 지정한 작동 범위를 벗어나면 모터 출력이 꺼집니다.
- 실시간은 아니고 어느정도 평균처리가 됩니다.
가감속 시간 지정 하기
- 가속 시간(Time Speed Up), 감속 시간(Time Speed Down)을 설정합니다.
- 추가로 비상 정지 시간(Time Speed ES: Emergency Stop)을 설정합니다.
- 이 기능은 사다리꼴 속도 프로파일을 구현합니다.
- 지정한 최대 속도까지 가속하는 시간, 최대 속도에서 속도 0까지 감속하는 시간을 지정할수 있습니다.
- 부드러운 가감속이 필요한 경우에 사용합니다.
- 일반적인 서보로서 사용할때는 0 으로 설정합니다.
- Time Speed Up/Down/ES 의 단위는 PX = PT / 10, PT = PID TIME 에 따라 달라집니다.
- 예를 들어
- PX = 1 이면: Time Speed Up = 100 = 100 msec 입니다.
- PX = 2 이면: Time Speed Up = 100 = 200 msec 입니다.
현재 속도 읽기
Register VELOCITY 를 읽으면 서보의 현재 속도를 알수 있습니다.
속도의 단위는 pos/100msec 입니다.
pos 의 단위는 16384 = 360 deg 입니다.
Vt (sec/60deg) 와 Vp (pos/100msec) 의 변환식은 다음과 같습니다.
- Vp = 60 x 16384 / 360 / Vt / 10
- Vt = 60 x 16384 / 360 / Vp / 10
ex) 1920 pos/100msec = 0.142 sec/60deg
현재 가속도 읽기
- Register ACC 를 읽으면 서보의 현재 가속도를 알수 있습니다.
서보 내부 온도 센서 종류
- CAN 서보는 제품에 따라 다양한 온도 센서를 가지고 있습니다.
- MCU 온도
- 제어 보드의 MCU 에 내장된 온도 센서의 데이터 입니다.
- 모터 온도
- 모터에 부착된 온도 센서의 데이터 입니다.
- 습도 센서의 온도
- 습도 센서에 포함된 온도 센서의 데이터 입니다.
- MCU 온도
- 온도에 의한 모터 출력 끄기
- MCU 온도의 최소, 최대 값을 각각 지정하여, 모터 출력을 끌 수 있습니다.
- 모터 온도, 습도 센서의 온도 데이터는 별도의 감시 코드가 없으므로, Host 에서 주기적으로 읽어서 판단하여 서보 출력을 끄거나 제어해야 합니다.
추가 기능
User Data
- Register 2개에 사용자가 원하는 정보를 넣어 둘수 있습니다.
- 값을 변경하고 SAVE 절차를 수행하면, Reset 되어도 유지됩니다.
Stream
- Register POSITION, CanServo/TURN 등의 정보를 지정한 간격으로 전송합니다.
- UAVCAN 에서는 Actuator Status 메시지를 발신합니다.
- CanServo/Stream 을 참조해 주십시오.
Stream Address
- 총 4개의 Register 를 통해, 원하는 주소 2개씩 최대 8개까지 지정 할수 있습니다.
- CanServo/Stream/Address 를 참조해 주십시오.
Stream CAN ID
- Stream CAN Packet 발신 때 사용할 CAN ID 를 별도 지정하는 기능입니다.
- CanServo/Stream/CAN ID 를 참조해 주십시오.
Start Position
- CAN 서보는 기동시 Reset 시점의 위치를 유지합니다.
- Reset 시점에 특정 위치로 이동시키고 싶을 때 사용하는 기능입니다.
- CanServo/Start Position 를 참조해 주십시오.
Fail Safe
- POSITION_NEW 가 일정 시간 동안 오지 않으면 특정 위치로 이동시키고 싶을 때 사용하는 기능입니다.
- 시간과 위치를 각각 설정합니다.
- CanServo/Fail Safe 를 참조해 주십시오.
Pause Stream
- Stream 발신을 일시적으로 정지시키는 기능입니다. 이 상태는 저장되지 않으며, 서보 Reset 이 되면 정지는 풀립니다.
- CanServo/Stream/Pause 를 참조해 주십시오.
Switch to Bootloader
- FW 실행 중에 Bootloader 로 전환하는 기능입니다.
- Bootloader 에서 사용할 통신 속도, CAN ID 등을 지정할수 있습니다.
- 이를 통해 각 서보가 모두 켜져 있는 상태에서 1대의 서보만 FW 를 업데이트 할수 있습니다.
- CanServo/Switch to Bootloader 를 참조해 주십시오.
기능별 구분
전류 측정 회로가 있는 경우
- MD 시리즈 일부 (예: MD89), SG 시리즈, RB 시리즈, DB 시리즈는 전류 측정 회로가 있습니다.
- 실시간 측정한 전압과 전류를 이용하여 출력을 조절합니다.
모터 온도 센서가 있는 경우
- 일부 모델에서는, 모터의 온도 데이터를 제공합니다.
- Host 에서 주기적으로 확인하여, 서보를 끄거나, 출력을 낮추어야 합니다.
전압 상승 방지 회로가 있는 경우
- 특정 전압 이상이 되지 못하도록 제한해 주는 회로가 장착된 모델이 있습니다.
- 예: SG50
- 서보는 동작 상황에 따라 발전이 되어 전압이 높아지는 경우가 있습니다.
- 예: 감속 동작, 윈치 내리기
- 이를 하드웨어적으로 방지하는 회로입니다.
- 다만, 한도를 넘어서면 전자 퓨즈에 의해 회로가 꺼지면서 기능이 멈춥니다.
- 이 회로가 꺼지면 그 다음으로 Over Voltage Brake 기능이 고전압을 잡아줍니다.
- SG50 의 경우에는 방지 회로가 1차로 막고, 2차로 Over Voltage Brake 기능이 막습니다.
습도 센서가 있는 경우
- 습도 센서가 추가로 있는 모델이 있습니다.
- 예: SG 시리즈 일부: SG33, SG50
- 습도 센서는 서보 내부의 상대 습도와 온도 데이터를 제공합니다.
- Low Data 를 그대로 제공하므로, 공식에 따라 계산해야 합니다.
- 주기적으로 데이터를 받아서, Host 에서 판단하여 서보를 끄거나, 동작을 제한해야 합니다.